Alberton Health Centre | Alberton, PEI

MARKET:
Institutional

CLIENT:
Pomerleau

PROJECT TEAM:
Pomerleau

PROJECT SERVICES:
Whole Building Air Tightness Testing
Thermographic Imaging

PROJECT DESCRIPTION

ThermalWise completed air tightness testing and air leakage site detection using thermographic imaging at two stages of construction. The first stage was conducted once all building envelope components were installed. The second stage was performed after all building components were in place and construction completed.

 General Air Tightness Testing Procedure (based on subsection 3.1.1 and 3.1.2 of section 07 27 00): the mean value of the air leakage flow through the exterior envelope for a negative and positive pressurization air leakage test must not exceed 0.25 CFM/ft2 @75Pa. Air leakage testing is required to be performed in general accordance with ASTM E779 with additional requirements included in the construction specification. 

 Building Air Leakage Site Detection: thermography-based air leakage site detection took place in conjunction with the air leakage testing for both Stage 1 and Stage 2 testing. This testing was performed in general accordance with ASTM 1186. 